Gas piston installation

Gas turbine unit BKGPEA-200.
Heat recovery system (HRS) gas turbine unit.

Recuperator of gas turbine unit used for premises heating

Result
During operation extra efficiency have been achieved

ЭPERFORMANCE PARAMETERS:

HOT SIDE

COLD SIDE

Inlet temperature, °С
550
-20

Outlet temperature, °С
160
40

Flow rate, Nm3 / h
800
5 700

Pressure drop in channels, mm. WG
14
44

Thermal power, kW
122