Recuperators for food industry

Bakery. Heating of premises
Bakery plant.

Electric baking oven.

Introduction of the heat exchanger for air preheating to ventilation system.

Implemented in 2013.

PERFORMANCE PARAMETERS:

HOT SIDE

COLD SIDE

Inlet temperature, °С
240
25

Outlet temperature, °С
168
50

Flow rate, Nm3 / h
2 838
2 838

Pressure drop in channels, mm. WG
8
40

Thermal power, kW
63

Bakery. Heating of industrial water.
Bakery plant.

Electric baking oven.

Introduction of the heat exchanger for heating of industrial water

Implemented in 2017.

PERFORMANCE PARAMETERS:

HOT SIDE

COLD SIDE

Inlet temperature, °С
260
5

Outlet temperature, °С
80
46

Flow rate, Nm3 / h
550
1

Pressure drop in channels, mm. WG
8
40

Thermal power, kW
38

Production of dry breakfast foods.
Oven for corn flakes roasting.

Implementation of the heat exchanger for preheating combustion air supplied to the burner.

Approved for implementation.

PERFORMANCE PARAMETERS:

HOT SIDE

COLD SIDE

Inlet temperature, °С
1 000
200

Outlet temperature, °С
887
350

Flow rate, Nm3 / h
1 500
1 350

Pressure drop in channels, mm. WG
10
14

Thermal power, kW
76

Brewery
Malt hothouse branch brewery.

Setting the drying of malt.

Introduction of the heat exchanger for air preheating to ventilation system.

Approved for implementation.

PERFORMANCE PARAMETERS:

HOT SIDE

COLD SIDE

Inlet temperature, °С
50
4

Outlet temperature, °С
19
34

Flow rate, Nm3 / h
900 000
900 000

Thermal power, kW
700

Greenhouse.
Boiler.

Installation of the heat exchanger for flue gas cooling and further supply to the carbon dioxide generation unit in the greenhouse.

New construction.

Approved for implementation.

PERFORMANCE PARAMETERS:

HOT SIDE

COLD SIDE

Inlet temperature, °С
200
5

Outlet temperature, °С
40
30

Flow rate, Nm3 / h
25 000
52

Pressure drop in channels, mm. WG
19
1 522

Thermal power, kW
1 511